YASKAWA P1000 Technical Manual page 281

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
U4-03
Cooling Fan Operation
(67)
Time
U4-04
Cooling Fan Maintenance Displays main cooling fan usage time as a percentage of its expected
(7E)
U4-05
Capacitor Maintenance
(7C)
U4-06
Soft Charge Bypass Relay
(07D6)
Maintenance
U4-07
IGBT Maintenance
(07D7)
U4-08
Heatsink Temperature
(68)
U4-09
LED Check
(5E)
U4-10
kWh, Lower 4 Digits
(5C)
U4-11
kWh, Upper 5 Digits
(5D)
U4-13
Peak Hold Current
(7CF)
U4-14
Peak Hold Output
(7D0)
Frequency
U4-16
Motor Overload Estimate
(7D8)
(oL1)
U4-18
Frequency Reference
(7DA)
Source Selection
Frequency Reference from
U4-19
MEMOBUS/Modbus
(7DB)
Comm.
U4-20
Option Frequency
(7DC)
Reference
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Description
Displays the cumulative operation time of the cooling fan. The default value
for the fan operation time is reset in parameter o4-03. The maximum
number displayed is 65535.
Note:
This monitor is only updated every 10 operating hours.
performance life. Parameter o4-03 can be used to reset this monitor.
Displays main circuit capacitor usage time as a percentage of their expected
performance life. Parameter o4-05 can be used to reset this monitor.
Displays the soft charge bypass relay maintenance time as a percentage of
its estimated performance life. Parameter o4-07 can be used to reset this
monitor.
Displays IGBT usage time as a percentage of the expected performance
life. Parameter o4-09 can be used to reset this monitor.
Displays the heatsink temperature.
Lights all segments of the LED to verify that the display is working
properly.
Monitors the drive output power. The value is shown as a 9-digit number
displayed across two monitor parameters, U4-10 and U4-11.
Example:
12345678.9 kWh is displayed as:
U4-10: 678.9 kWh
U4-11: 12345 MWh
Displays the highest current value that occurred during run.
Displays the output frequency when the current value shown in U4-13
occurred.
Shows the value of the motor overload detection accumulator. 100% is
equal to the oL1 detection level.
Displays the source for the frequency reference as XY-nn.
X: indicates which reference is used:
0 = OFF
1 = AUTO
2 = HAND
Y-nn: indicates the reference source
0-01 = HOA keypad
1-00 = Analog (not assigned)
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
1-03 = Analog (terminal A3)
2-02 to 17 = Multi-step speed (d1-02 to 17)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
9-01 = Up/Down
Displays the frequency reference provided by MEMOBUS/Modbus
(decimal).
Displays the frequency reference input by an option card (decimal).
B.13 U: Monitors
Analog Output
Unit
Level
No signal output
1 h
available
No signal output
1%
available
No signal output
1%
available
No signal output
1%
available
No signal output
1%
available
10 V: 100 °C
1 °C
No signal output
available
No signal output
1 kWh
available
No signal output
1 MWh
available
No signal output
0.01 A
available
<1>
No signal output
0.01 Hz
available
10 V: 100%
0.1%
No signal output
available
No signal output
0.01%
available
No signal output
available
281