5.7 H: Terminal Functions
10 V
Output Voltage
5 V
0 V
0%
Example 3: Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.
10 V
Output Voltage
3 V
0 V
0%
n
H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
Set jumper S5 on the terminal board accordingly when changing these parameters.
No.
H4-07
H4-08
Setting 0: 0 to 10 V
Setting 1: -10 to +10 V
Setting 2: 4 to 20 mA
132
H4-07, 08 = 0
Gain 150%
Bias 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
100%
Monitor Value
Figure 5.40 Analog Output Gain and Bias Setting Example 1 and 2
H4-07, 08 = 0
Bias 30%
Gain 100%
Bias 0%
Gain 100%
100%
Monitor Value
Figure 5.41 Analog Output Gain and Bias Setting Example 3
Name
Multi-Function Analog Output Terminal FM
Signal Level Selection
Multi-Function Analog Output Terminal AM
Signal Level Selection
H4-07, 08 = 1
15 V
Output Voltage
10 V
5 V
-100%
H4-07, 08 = 1
10V
Output Voltage
3 V
-100%
Setting Range
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Gain = 150%
Bias = 0%
Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%
100%
Monitor Value
-5 V
-10 V
-15 V
Gain = 100%
Bias = 30%
Gain = 100%
Bias = 0%
100%
Monitor Value
-4 V
-10 V
Default
0 to 2
0 to 2
0
0