5.6 F: Options

5.6

F: Options

u

F6: Drive/Bypass Communications

n
F6-01: Communications Error Operation Selection
Determines drive operation when a communication error occurs.
No.
F6-01
Setting 0: Ramp to Stop (Use the Deceleration Time Set to C1-02)
Setting 1: Coast to Stop
Setting 2: Fast Stop (Use the Fast Stop Time Set to C1-09)
Setting 3: Alarm Only (Continue Operation)
Setting 4: Alarm Only (Continue Operation Using the Frequency Reference Set in d1-04)
n
F6-02: External Fault from Bypass Controller Detection Selection
Determines the detection method of an external fault initiated by the bypass controller (EF0).
No.
F6-02
External Fault from Bypass Controller Detection Selection
Setting 0: Always detected
Setting 1: Detection during Run only
n
F6-03: External Fault from Bypass Controller Operation Selection
Determines drive operation when an external fault is initiated by the bypass controller (EF0).
No.
F6-03
External Fault from Bypass Controller Operation Selection
Setting 0: Ramp to stop
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
114
Parameter Name
Communications Error Operation Selection
Parameter Name
Parameter Name
Setting Range
Setting Range
Setting Range
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Default
0 to 4
Default
0, 1
Default
0 to 3
1
0