H Parameters: Multi-Function Terminals; H Parameters: Multi-Function Terminals; H1: Multi-Function Digital Inputs - YASKAWA P1000 Technical Manual

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

B.8 H Parameters: Multi-Function Terminals
B.8 H Parameters: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
u

H1: Multi-Function Digital Inputs

No.
(Addr.
Name
Hex)
Multi-Function Digital Input
H1-03
Terminal S3 Function
(400)
Selection
Multi-Function Digital Input
H1-04
Terminal S4 Function
(401)
Selection
Multi-Function Digital Input
H1-05
Terminal S5 Function
(402)
Selection
Multi-Function Digital Input
H1-06
Terminal S6 Function
(403)
Selection
Multi-Function Digital Input
H1-07
Terminal S7 Function
(404)
Selection
Multi-Function Digital Input
H1-08
Terminal S8 Function
(405)
Selection
H1-oo
Function
Setting
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
6
Jog reference selection
C
Analog terminal input selection
<1>
Not Used (Through Mode)
F
10
Up command
11
Down command
<2>
Reverse Jog
13
14
Fault Reset
19
PID disable
24
External fault
60
DC Injection Braking command
<1> Available in bypass controller software versions VST800298 and later.
<2> Available in bypass controller software versions VST800297 and earlier.
262
Assigns a function to the multi-function digital inputs through Z2-oo = 3.
Refer to
Table B.3
for descriptions of setting values.
Note:
Set unused terminals to F.
Assigns a function to the multi-function digital inputs through Z2-oo = 4.
Refer to
Table B.3
for descriptions of setting values.
Note:
Set unused terminals to F.
Assigns a function to the multi-function digital inputs through Z2-oo = 5.
Refer to
Table B.3
for descriptions of setting values.
Note:
Set unused terminals to F.
Assigns a function to the multi-function digital inputs through Z2-oo = 6.
Refer to
Table B.3
for descriptions of setting values.
Note:
Set unused terminals to F.
Assigns a function to the multi-function digital inputs through Z2-oo = 7.
Refer to
Table B.3
for descriptions of setting values.
Note:
Set unused terminals to F.
Assigns a function to the multi-function digital inputs through Z2-oo = 8.
Refer to
Table B.3
for descriptions of setting values.
Note:
Set unused terminals to F.
Table B.3 H1 Multi-Function Digital Input Selections
When input terminals are set to Multi-Step Speed References 1 through 3, switching
combinations of those terminals will create a multi-step speed sequence using the frequency
references set in d1-01 through d1-08.
When input terminals are set to Multi-Step Speed References 1 through 3, switching
combinations of those terminals will create a multi-step speed sequence using the frequency
references set in d1-01 through d1-08.
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other reference
sources.
Open: Function assigned by H3-14 is disabled.
Closed: Function assigned by H3-14 is enabled.
Allows serial communications to control the output.
The drive accelerates when the Up command terminal closes, and decelerates when the Down
command closes. When both terminals are closed or both are open, the drive holds the
frequency reference. The Up and Down commands must always be used in conjunction with
one another.
The drive accelerates when the Up command terminal closes, and decelerates when the Down
command closes. When both terminals are closed or both are open, the drive holds the
frequency reference. The Up and Down commands must always be used in conjunction with
one another.
Closed: Runs reverse at the Jog frequency d1-17
Closed: Resets faults if the cause is cleared and the Run command is removed.
Open: PID control enabled
Closed: PID control disabled
Normally Open, Always Detected, Coast to Stop
Closed: Triggers DC Injection Braking.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Description
Description
Values
Page
Default: 24
Min.: 3
115
Max.: 60
Default: 14
Min.: 3
115
Max.: 60
Default: 3
Min.: 3
115
Max.: 60
Default: 4
Min.: 3
115
Max.: 60
Default: 6
Min.: 3
115
Max.: 60
Default: F
Min.: 3
115
Max.: 60
Page
115
115
115
115
115
115
115
116
117
117
117
117

Advertisement

Table of Contents
loading

Table of Contents