5.2 b: Application
DC Injection Braking time is determined by the value set to b2-04 and the output frequency at the time the Run command is
removed. It can be calculated by:
Note:
If an overcurrent (oC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the fault no
longer occurs.
Setting 3: Coast with Timer
When the Run command is removed, the drive will turn off its output and the motor will coast to stop. The drive will not start
if a Run command is input before the time t (C1-02) has expired. Cycle the Run command that was activated during time t
after t has expired to start the drive.
The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.
n
b1-04: Reverse Operation Selection
Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause
problems (e.g., air handling units, pumps, etc.).
No.
b1-04
84
DC Injection brake time
DC Injection braking time
b2-04×10
b2-04
Output frequency when
10%
Stop command was entered
Figure 5.3 DC Injection Braking Time Depending on Output Frequency
Run command
ON
Output
frequency
Figure 5.4 Coast with Timer
Run wait time t
Active deceleration time
Momentary Power Loss
Minimum Baseblock
Time (L2-03)
Min output
frequency
Figure 5.5 Run Wait Time Depending on Output Frequency
Parameter Name
Reverse Operation Selection
(b2-04) x 10 x Output frequency
=
Max. output frequency (E1-04)
100%
(Maximum output
frequency)
OFF
ON
Drive output shut off
Run wait time t
Output frequency
when Stop command
was entered
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
OFF
ON
100%
(Max output
frequency)
Setting Range
0, 1
Default
1