H5: Memobus/Modbus Serial Communication - YASKAWA P1000 Technical Manual

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
Multi-Function Analog
H4-04
Output Terminal AM
(420)
Monitor Selection
H4-05
Multi-Function Analog
(421)
Output Terminal AM
Gain
H4-06
Multi-Function Analog
(422)
Output Terminal AM
Bias
Multi-Function Analog
H4-07
Output Terminal FM
(423)
Signal Level Selection
Multi-Function Analog
H4-08
Output Terminal AM
(424)
Signal Level Selection
u

H5: MEMOBUS/Modbus Serial Communication

No.
(Addr.
Name
Hex)
H5-04
Stopping Method after
(428)
Communication Error (CE)
<1>
<1> Parameter is only available in bypass controller software versions VST800297 and earlier.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
LCD Display
Selects the data to be output through multi-function analog
output terminal AM.
Terminal AM Sel
Set the desired monitor parameter to the digits available in
Uo-oo.
For example, enter "103" for U1-03.
Sets the signal level at terminal AM that is equal to 100% of
the selected monitor value.
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 0% of the
selected monitor value.
Terminal AM Bias
0: 0 to 10 V
Term FM Lvl Sel
1: -10 to +10 V
2: 4 to 20 mA
0: 0 to 10 V
Term AM Lvl Sel
1: -10 to +10 V
2: 4 to 20 mA
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm only
B.8 H Parameters: Multi-Function Terminals
Description
Description
Values
Page
Default: 103
Range: 000 to
131
621
Default: 50.0%
Min.: -999.9
131
Max.: 999.9
Default: 0.0%
Min.: -999.9
131
Max.: 999.9
Default: 0
132
Range: 0 to 2
Default: 0
132
Range: 0 to 2
Values
Page
Default: 3
133
Range: 0 to 3
265