5.13 Z: Bypass Parameters
n
Z1-14: Run Delay Frequency Reference
Sets the frequency used while delaying the Run command.
No.
Z1-14
<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.
n
Z1-15: Interlock Wait Time
When an input is programmed for Interlock and the time set to this parameter is reached before the Interlock input goes active,
a fault will be declared. The default setting of 0.0 will never time out.
No.
Z1-15
Run Delay with Preset Speed Examples
DAMPER ACTUATOR OUTPUT
VFD FREQUENCY REFERENCE
VFD OUTPUT FREQUENCY
166
Name
Run Delay Frequency Reference
Name
Interlock Wait Time
VFD RUN COMMAND
BAS INTERLOCK INPUT
Figure 5.57 Run Delay with Preset Speed Example: Default Setting
t1
t2
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Setting Range
<1>
0.0 to 60.0 Hz
Setting Range
0.0 to 300.0 s
t3
Default
<1>
60.0 Hz
Default
0.0 s