YASKAWA P1000 Technical Manual page 383

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

Continue at Last Speed with Alarm
For this condition, Communication Fault Enable (BO 11) must be enabled and Cable Loss Speed (AO 22) should be set to a
value other than 0. An AL14 Serial Communications Alarm is shown.
Continue at Preset Speed with Alarm
In this mode, Cable Loss Timeout (AO 21) is set to the desired interval, Cable Loss Speed (AO 22) is set to the desired preset
speed and Z3–05 is set to "4". If the time between messages exceeds the timeout interval, the drive speed command (AO 1)
is set to the Cable Loss Speed (AO 22) and the drive continues running at this new speed. Communication Fault Enable (BO
11) must be set to 'On'.
Stop with Fault (FB14)
Communication Fault Enable (BO 11) must be set to 'On'. In this mode, Cable Loss Timeout (AO 21) is set to the desired
interval and parameter F6-03 is set to a value of 0,1 or 2. If the time between messages exceeds the timeout interval, the drive
will declare an EF0 fault and the drive speed command (AO 1) will be set to 0. The stopping method is determined by the
setting of F6-03.
• F6-03 = 0 selects Ramp to Stop. The deceleration time or the slope of the ramp is determined by the setting of drive parameter
C1-02
• F6-03 = 1 selects Coast to Stop. The drive does not attempt to control the rate of deceleration.
• F6-03 = 2 selects Emergency or Fast Stop. The deceleration time is determined by the setting of drive parameter C1-09.
n
Bypass Fault Numbers
Fault Code
0002H
Undervoltage (Uv1)
0003H
Control Power Supply Undervoltage (Uv2)
0004H
Soft Charge Circuit Fault (Uv3)
0006H
Ground Fault (GF)
0007H
Overcurrent (oC)
0008H
Overvoltage (ov)
0009H
Heatsink Overheat (oH)
000AH
Heatsink Overheat (oH1)
000BH
Motor Overload (oL1)
000CH
Drive Overload (oL2)
000DH
Overtorque Detection 1 (oL3)
0010H
Braking Resistor Overheat (rH)
0011H
External Fault at Input Terminal S3 (EF3)
0012H
External Fault at Input Terminal S4 (EF4)
0013H
External Fault at Input Terminal S5 (EF5)
0014H
External Fault at Input Terminal S6 (EF6)
0015H
External Fault at Input Terminal S7 (EF7)
001BH
Input Phase Loss (PF)
001CH
Output Phase Loss (LF)
001DH
Motor Overheat (PTC input) (oH3)
001EH
Digital Operator Connection (oPr)
001FH
EEPROM Write Error (Err)
0020H
Motor Overheat (PTC input) (oH4)
0021H
MEMOBUS/Modbus Communication Error (CE)
0022H
Option Communication Error (bUS)
0027H
Option External Fault (EF0)
0028H
PID Feedback Loss (FbL)
0029H
Undertorque Detection 1 (UL3)
002BH
High Slip Braking Overload (oL7)
0030H
Hardware Fault (including oFx)
0036H
Output Current Imbalance (LF2)
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Table G.3 Fault Trace / History Register Contents
Fault Name
G.4 Bypass Operations by N2
Fault Code
0037H
Pullout Detection (Sto)
003BH
Too Many Speed Search Restarts (SEr)
0041H
PID Feedback Loss (FbH)
0042H
External Fault 1, Input Terminal S1 (EF1)
0043H
External Fault 2, Input Terminal S2 (EF2)
0046H
Current Offset Fault (CoF)
0047H
PLC Detection Error 1 (PE1)
0048H
PLC Detection Error 2 (PE2)
004DH
Output Voltage Detection Fault (voF)
0052H
Node Setup Fault (nSE)
005AH
Motor Underload Protection (UL6)
0083H
A/D Conversion Error (CPF02)
0084H
PWM Data Fault (CPF03)
0087H
EEPROM Memory Data Error (CPF06)
0088H
Terminal Board Connection Error (CPF07)
0089H
EEPROM Serial Communication Fault (CPF08)
008CH
RAM Fault (CPF11)
008DH
Flash Memory Circuit Exception (CPF12)
008EH
Watchdog Circuit Exception (CPF13)
008FH
Control Circuit Fault (CPF14)
0091H
Clock Fault (CPF16)
0092H
Timing Fault (CPF17)
0093H
Control Circuit Fault (CPF18)
0094H
Control Circuit Fault (CPF19)
0095H
Hardware Fault at Power Up (CPF20)
0096H
Hardware Fault at Communication Start Up (CPF21)
0097H
A/D Conversion Fault (CPF22)
0098H
PWM Feedback Fault (CPF23)
0099H
Drive Unit Signal Fault (CPF24)
009AH
Terminal Board is Not Properly Connected. (CPF25)
009BH
ASIC BB Circuit Error (CPF26)
Fault Name
383
G

Advertisement

Table of Contents
loading

Table of Contents