Connecting To A Network; Connecting To A Network; Network Cable Connection - YASKAWA P1000 Technical Manual

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

G.2 Connecting to a Network
This section explains how to connect the drive to an N2 network and the network termination required for a connection.
u

Network Cable Connection

Follow the instructions below to connect the bypass to a N2 network.
1.
With the power shut off, connect the communications cable to the bypass controller board A2 and the master. Use
terminal TB3 for N2.
Note:
Separate the communications cables from the main circuit cables and other wiring and power cables. Use shielded cables for
the communications cables, and properly shielded clamps to prevent problems caused by electrical interference.
2.
Check or set the termination resistor selection at all slaves. Refer to the description in the Network Termination
section for details on the termination resistor.
3.
Switch the power on.
4.
Set the parameters needed for serial communications (Z3-01 through Z3-11) using the digital operator.
5.
Shut the power off and wait until the display on the digital operator goes out completely.
6.
Turn the power back on.
7.
The bypass is now ready to begin communicating with the master.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
TB3
4
3
2
1
Figure G.2 Serial Communications Cable Connection Terminal (TB3)
SHLD
Shield
Transmit/Receive (-)
TXRX-
Transmit/Receive (+)
TXRX+
IG5
Isolated Ground Reference
G.2 Connecting to a Network
G
377

Advertisement

Table of Contents
loading

Table of Contents