Three-Phase 208 Vac Bypass Drive Models D273 To D396; Three-Phase 480 Vac Bypass Drive Models B001 To B027 - YASKAWA P1000 Technical Manual

Ac drive
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

u

Three-Phase 208 Vac Bypass Drive Models D273 to D396

Item
Bypass Model P1Bo
Maximum Applicable
Motor Capacity (HP)
Input Current Range (A)
Input
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Rated Output Current (A)
Output
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.
<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
u

Three-Phase 480 Vac Bypass Drive Models B001 to B027

Item
Bypass Model P1Bo
Maximum Applicable
Motor Capacity (HP)
Input Current Range (A)
Rated Voltage
Rated Frequency
Input
Allowable Voltage
Fluctuation
Allowable Frequency
Fluctuation
Rated Output Current (A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency
(Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.
<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Table A.3 Power Ratings (Three-Phase 208 Vac)
<1>
<2>
Rated Voltage
Rated Frequency
Overload Tolerance
<3>
Carrier Frequency
Table A.4 Power Ratings (Three-Phase 480 Vac)
B001
B002
0.75
1
<1>
1.6
2.1
<2>
to 2.4
to 2.9
1.6
2.1
(Derating may be required for applications that start and stop frequently)
<3>
Specification
D273
100
284.9 to 287.1
376.8 to 380.2
Three-phase 208 Vac 50/60 Hz
273
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
User-adjustable between 2 and 10 kHz
Three-phase 208 Vac
400 Hz (user-set)
Specification
B003
B004
B007
2
3
5
3.6
5.2
8.1
to 4.4
to 6.1
to 9.0
Three-phase 480 Vac 50/60 Hz
-15 to 10%
±5%
3.4
4.8
7.6
ND Rating: 120% of rated output current for 60 s
User-adjustable between 2 and 15 kHz
Three-phase 480 Vac
400 Hz (user-set)
A.1 Power Ratings
D343
D396
125
150
450.9 to 454.2
-15 to 10%
±5%
343
396
B011
B014
B021
7.5
10
15
13.9
16.0
21.9
to 14.7
to 16.7
to 22.6
11.0
14.0
21.0
B027
20
33.1
to 33.8
27.0
A
241