Advertisement

5.13 Z: Bypass Parameters
No.
Name
Setting Range
Default
Z1-08
Run Command Select
0 to 3
1
Setting 0: HOA Keypad
Setting 1: Bypass Controller Digital Input
This setting requires entering the Run command via the digital input terminals.
Setting 2: BACnet or MEMOBUS/Modbus Communications
This setting requires entering the Run command via serial communications by connecting the RS-485 serial communication
cable to control terminals TXRX+ and TXRX- on the terminal block.
Refer to MEMOBUS/Modbus Configuration on page
326
for instructions.
Setting 3: Option Card
This setting requires entering the Run command via the communication option board by plugging a communication option
board into the CN5 port on the control PCB. Refer to the option card manual for instructions on integrating the bypass into
the communication system.