C.4 BACnet Setup Parameters
n
Z3-08, Z3-09: BACnet Device Object Identifier
These parameters set the Instance Identifier of the BACnet Device Object, where Z3-08 is the least significant word and Z3-09
is the most significant word.
No.
Z3-08
Z3-09
Example 1: Set Device Object Instance Identifier of "1234".
1234 decimal is equal to 4D2H (hexadecimal).
Set Z3-08 to 4D2H and set Z3-09 to 0.
Example 2: Set Device Object Instance Identifier of "123456".
123456 decimal is equal to 1E240H.
Set Z3-08 to D687H and set Z3-09 to 12H.
312
Name
BACnet Device Object Identifier 0
BACnet Device Object Identifier 1
Setting Range
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Default
0 to FFFFH
0 to 003FH
1
0