4.3 The Drive and Programming Modes
u

Simplified Setup Using the Quick Setting Group

The Quick Setting Group lists only the basic parameters necessary to set up the P1000 Bypass. This group expedites the startup
process by showing only the most important parameters.
n
Quick Setting Parameters
Table 4.5
lists the parameters in the Quick Setting Group.
Use the Programming Mode to access parameters not displayed in the Quick Setting Group.
No.
Name
Z1-07
Speed Reference Select
(85CC)
Spd Ref Sel
Z1-08
Run Command Select
(85CD)
Run Cmd Sel
Z1-09
HAND Mode Drive Speed
(85CE)
Reference
Hand Fref
Z1-37
Set Time
(85EA)
Set Time
Z3-01
Serial Communications
(8500)
Protocol Select
Serial Protocol
Application Preset
A1-06
Application Sel
(127)
E1-01
Input Voltage Setting
Input Voltage
(300)
Maximum Voltage
E1-05
(304)
Max Voltage
Motor Rated Current
E2-01
Motor Rated FLA
(030E)
Z3-02
Serial Communications
(8501)
Node Address Select
Node Address
68
Table 4.5 Quick Setting Group Parameters
Determines the source of the Frequency Reference sent from the Bypass
Controller to the Drive.
0: Operator
1: Analog Input
2: Bypass Serial
3: Option Board (CN5)
Determines the source of the Auto Mode Run command used by the Bypass
Controller.
0: Operator
1: Bypass Controller Digital Input
2: Bypass Serial
3: Option Board (CN5)
This is the speed reference used when the Drive is running in HAND mode.
Units are in Hz.
Changes the LCD display to time setting to set the Real Time Clock.
0: Normal display
1: Displays time and date setting modes
<5>
2: Reset time
Selects the bypass serial communications protocol.
0: Modbus
1: N2
2: P1
3: BACnet
0: General-purpose
8: Pump
9: Pump w/PI
10: Fan
11: Fan w/PI
Note:
This parameter is not settable. It is used as a monitor only.
This parameter must be set to the power supply voltage.
WARNING! Electrical Shock Hazard. Drive input voltage (not motor
voltage) must be set in E1-01 for the protective features of the drive to
function properly. Failure to do so may result in equipment damage
and/or death or personal injury.
Only applicable when E1-03 is set to F.
Sets the motor nameplate full load current in amps. Automatically set during
Auto-Tuning.
Selects the bypass serial communications node address.
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Description
Values
Page
<4>
Default: 1
162
Range: 0 to 3
Default: 1
163
Range: 0 to 3
Default: 10.0 Hz
<1>
165
Min.: 0.0
Max.: 60.0
Default: 0
172
Range: 0 to 2
Default: 3
177
Range: 0, 3
Default: 0
82
Range: 0; 8 to 11
Default: 460 V
<1>
109
Min.: 310
<1>
Max.: 510
<3>
Default:
Min.: 0.0 V
112
<1>
Max.: 510.0 V
<1>
Default:
Min.: 10% of drive
rated current
113
Max.: 200% of
drive rated current
<2>
Default: 1
Min.: 0
177
Max.: 127