Status
Open
Drive is not in a baseblock state.
Closed
Baseblock is being executed.
Settings B and 17: Torque Detection 1 (N.O., N.C.)
These digital output functions signal an overtorque or undertorque situation to an external device.
Set up the torque detection levels and select the output function from the table below.
Setting
Status
B
Closed
17
Open
Setting C: Frequency Reference Loss
The output closes when frequency reference loss is detected.
Setting E: Fault
The output closes when the drive faults (excluding CPF00 and CPF01 faults).
Setting F: Through Mode
Select this setting when using the terminal in a pass-through mode. When set to F, an output does not trigger any function in
the drive. Setting F, however, still allows the output status to be read by a PLC via a communication option or MEMOBUS/
Modbus communications.
Setting 10: Minor Fault
The output closes when a minor fault condition is present.
Setting 11: Fault Reset Command Active
The output closes when there is an attempt to reset a fault situation from the control circuit terminals, via serial communications,
or using a communications option card.
Setting 13: Speed Agree 2 (f
The output closes when the actual output frequency or motor speed is within the speed agree width (L4-04) of the current
frequency reference, regardless of the direction.
Status
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed
Output frequency or motor speed is within the range of frequency reference ±L4-04.
Note:
Detection works in forward and reverse.
Output Frequency
Speed Agree 2
Setting 14: User-Set Speed Agree 2 (f
The output closes when the actual output frequency or motor speed and the frequency reference are within the speed agree
width (L4-04) of the programmed speed agree level (L4-03).
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Torque detection 1 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
Torque detection 1 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
/f
Agree 2)
ref
out
Frequency
reference
or Motor Speed
OFF
ON
Figure 5.29 Speed Agree 2 Time Chart
/f
Agree 2)
ref
set
Description
Description
Description
L4-04
5.7 H: Terminal Functions
L4-04
5