Configuration; Parameterizing The Module Via Profinet; Selecting The Module; Configure The Profinet Station Name And Ip Address - WAGO 765-1103/100-000 Manual

16-channel digital output; profinet; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

Commissioning
• Click OK.
The module is now accessible via the IP address, and you can open WAGO Web-
server I/O Field with a browser, for example.

10.2 Configuration

10.2.1 Parameterizing the Module via PROFINET

ü To configure the PROFINET IO-Controllers, you need the GSDML file.
1. Import the GSDML file.
2. Select the module from the device catalog.
3. Configure the ports.
4. Set the parameters.
ð The parameters are imported from the GSDML file.

10.2.1.1 Selecting the Module

Select the module used from the device catalog.
Module: 765-1103
Designation: 16DO FLD PN 24 VDC 2.0 A

10.2.1.2 Configure the PROFINET Station Name and IP Address

When delivered and after a factory rest, the IO device has no PROFINET product name,
and the IP address is 0.0.0.0.
The IO-Device requires a unique PROFINET product name so the IO controller can com-
municate with the IO device.
Use the engineering software to assign the IO device a PROFINET product name.
The IO controller configures the IP address when PROFINET starts up.

10.2.1.3 Parameterizing Ports

Parameterize the ports using the information in section
figuration

10.2.1.4 Setting Parameters

Parameterize the submodule to adjust the port functions and basic settings.
You can find all the module parameters in

10.3 Parameterization

The following tools are described below:
8 WAGO Webserver I/O Field [} 57]
8 WAGO I/O Field app [} 75]
8 OPC UA Server [} 75]
56
Product manual | Version: 2.2.0
16DO FLD PN DC 24V 2.0A
[} 41].
8 Setting the PROFINET Con-
8 PROFINET Parameters
765-1103/100-000
[} 40].