Set Up the Dry Contact Alerts

You can connect the S1, S2, S3 and S4 terminals on the
EIM to a dry contact device to display an alert. Dry contact
alerts include Full Drain Pan, Dirty Filter, Water Leak,
System Shutdown, Service Needed, Fan Failure and
Custom Alert. Dry contact device can be normally open
(shown in diagram) or normally closed.
MULTIPLE DRY CONTACT DEVICES
ON ONE SET OF TERMINALS
1. Wire the dry contact device to S1, S2, S3 or S4 termi-
nals at the EIM.
2. Enter Installer Setup (see "Make Changes to Installer
Setup" beginning on page 21).
3. Dry Contacts are selected at ISU 600. Select the
appropriate Dry Contact(s) and press Next.
Fig. 158.
4. Select the terminals wired to the Dry Contact device,
and press Next.
Fig. 159.
ONE DRY CONTACT DEVICE
EIM
S4
S4
S3
S3
Fig. 157. Wiring dry contact devices.
WARNING
Equipment Damage Hazard.
Do not apply power to S1, S2, S3 or S4 terminals. Do
not connect a temperature sensor to the S1, S2, S3
or S4 terminals if setup for a dry contact device.
IMPORTANT
The dry contact device must be rated for low volt-
age.
NOTE: You can connect multiple Dry Contact devices in
parallel to the S1, S2, S3 or S4 terminals.
ONE DRY CONTACT DEVICE
EIM
MULTIPLE DRY CONTACT DEVICES
ON ONE SET OF TERMINALS
5. Select Normally Open or Normally Closed, and press
Next.
NOTE: For example, if a wet switch is normally open,
it will close when the device detects water. If
the wet switch is normally closed, it will open
when the device detects water.
Refer to the instructions packed with the dry
contact device to determine if it is normally
open or normally closed.
75
®
VISIONPRO
8000 WITH REDLINK™
Fig. 160.