Wiring - Honeywell Home VisionPRO 8000 Manual

With redlink
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH REDLINK™
At the Indoor Sensor, RedLINK Internet Gateway, Entry/Exit Remote, Vent-Filter Boost
Remote or TrueSTEAM Wireless Adapter
1. Press and hold the CONNECT button on the accessory until the status light glows amber (hold for about 10 seconds).
2. To reconnect the thermostat, go to "Linking RedLINK Accessories" beginning on page 15.

WIRING

See Table 10 for Equipment Interface Module terminal descriptions and Table 11 for thermostat terminal descriptions.
Table 10. Equipment Interface Module Terminal Designation Descriptions.
Conventional System
Terminal
C
Common wire from 24 VAC transformer.
R*
Power wire from 24 VAC transformer.
RH*
Heating power
RC*
Cooling power
W
Heat Stage 1
W2
Heat Stage 2
W3
Heat Stage 3
Y
Compressor Stage 1
Y2
Compressor Stage 2
G
Fan Relay
A
Connect to Economizer Module or Lighting
Panel (TOD).
Relay for humidification, dehumidification,
U1 / U1
ventilation, or a stage of heating/cooling. U
U2 / U2
terminals are dry contacts that require power.
U3 / U3
Input for a wired indoor sensor, outdoor sensor,
S1 / S1
discharge sensor, return sensor, dry contact
S2 / S2
device for alerts or dry contact device for
S3 / S3
remote setback.
S4 / S4
A
Connect to THM4000R1000 Wireless Adapter
B
for extended wireless range.
C
D
* Remove jumpers when separate transformers are used.
See "Wiring IAQ Equipment or a Heat/Cool Stage to the Terminals" beginning on page 131.
See "Dry Contact Alerts" beginning on page 74 for wiring Dry Contact Devices to display alerts.
68-0312—06
Description
Heat Pump
Terminal
C
Common wire from 24 VAC transformer.
R
Power wire from 24 VAC transformer.
RH
Heating power
RC
Cooling power
O/B
Changeover valve for heat pumps
AUX 1
Backup Heat Stage 1/Emergency Heat Stage 1
AUX 2
Backup Heat Stage 2/Emergency Heat Stage 2
Y
Compressor Stage 1
Y2
Compressor Stage 2
G
Fan Relay
L/A
Connect to Compressor Monitor, Zone Panel,
Economizer Module or Lighting Panel (TOD).
Relay for humidification, dehumidification,
U1 / U1
ventilation, or a stage of heating/cooling. U
U2 / U2
terminals are dry contacts that require power.
U3 / U3
Input for a wired indoor sensor, outdoor sensor,
S1 / S1
discharge sensor, return sensor, dry contact
S2 / S2
device for alerts or dry contact device for
S3 / S3
remote setback.
S4 / S4
A
Connect to THM4000R1000 Wireless Adapter
B
for extended wireless range.
C
D
118
Description