VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
Off
406
Max. Heat Recovery
Outdoor Temp
-20° F to 100° F
Off
407
Min. Cool Recovery
1° F/hr to 20° F/hr
Ramp Rate
68-0312—06
Table 3. Installer Setup (ISU) Table. (Continued)
Settings
Default
40° F
3° F/hr
Residential,
Commercial
Requires
or Both
EIM
Commercial
No
Commercial
No
38
Notes
Off: The heating system will begin recovery at the
time that is scheduled.
When a Maximum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Maximum Recovery Ramp Rate based on the
rate that the heating system can recover at for a
mild day in your region. Default setting is 8° F /
hour.
Set an Outdoor Temperature that is representative
of a mild day in your region to be associated with
the Maximum Recovery Ramp Rate. The
thermostat will begin recovery at the optimal time
based on a calculated ramp rate, allowing the
system to recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature.
Off: The cooling system will begin recovery at the
time that is scheduled.
When a Minimum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Minimum Recovery Ramp Rate based on the
rate that the cooling system can recover at for a
hot day in your region. Default setting is 3° F /
hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a hot day in
your region to be associated with the Minimum
Recovery Ramp Rate. The thermostat will begin
recovery at the optimal time based on a calculated
ramp rate, allowing the system to recover on time
and save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.