Remote Setback (Commercial Use)

The thermostat allows you to do REMOTE SETBACK when
set up for commercial use. This feature requires an
occupancy sensor connected to the S1, S2, S3 or S4
terminals at the Equipment Interface Module.
During Occupied program periods, an occupancy sensor
directs the thermostat to go to REMOTE SETBACK settings
when the room is empty. If someone is in the room, it uses
the Occupied program period settings. The thermostat
ignores the occupancy sensor during Unoccupied program
periods.
If the thermostat is set up to be non-programmable, the
sensor directs the thermostat to go to REMOTE SETBACK
settings when the room is empty. If someone is in the room,
then it follows the settings set by the user.
Depending on how your thermostat was installed, it may
delay for up to 30 minutes before switching to REMOTE
SETBACK settings. This delay allows the room to stay
comfortable if the room is unoccupied for only a short time.
Set Up Remote Setback
1. Select "Remote Setback" as shown in Fig. 291.
Fig. 291.
2. Select the terminals wired to the Remote Setback Dry
Contact device (occupancy sensor) and press Next.
3. Select Normally Open when Occupied or Normally
Closed when Occupied based on the type of dry con-
tact device installed.
NOTE: Normally Open when Occupied: The Dry
Contact device is open when the room is
occupied and will close when the room is
unoccupied.
Normally Closed when Occupied: The Dry
Contact device is closed when the room is
occupied and will open when the room is
unoccupied.
107
®
VISIONPRO
8000 WITH REDLINK™
Fig. 292.
68-0312—06