Honeywell Home VisionPRO 8000 Manual page 33

With redlink
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
1 to 12 CPH
315
Heat Cycles Per
Hour Stage 1
Note: Depending on
the application, the
text displayed on
the screen may
show the specific
heating equipment
type. "Stage 1" is
not displayed if
there is only 1
stage.
1 to 12 CPH
315
Heat Cycles Per
Hour Stage 2
Note: Depending on
the application, the
text displayed on
the screen may
show the specific
heating equipment
type.
Table 3. Installer Setup (ISU) Table. (Continued)
Settings
Default
Conv. Forced Air
= 5 CPH
Heat Pump = 3
CPH
Radiant Heat = 3
CPH
Conv. Forced Air
= 5 CPH
Heat Pump =
3 CPH
Radiant Heat = 3
CPH
33
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Both
No
This ISU is only displayed when ISU 207 Heat
Stages is set to 1 stage.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period measured
at a 50% load. For example, when set to 3 CPH, at
a 50% load, the most the system will cycle is 3
times per hour (10 minutes on, 10 minutes off).
The system cycles less often when load conditions
are less than or greater than a 50% load. The
recommended cycle rate settings are below for
each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
Both
No
This ISU is only displayed when ISU 207 Heat
Stages is set to 2 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period measured
at a 50% load. For example, when set to 3 CPH, at
a 50% load, the most the system will cycle is 3
times per hour (10 minutes on, 10 minutes off).
The system cycles less often when load conditions
are less than or greater than a 50% load. The
recommended cycle rate settings are below for
each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
®
8000 WITH REDLINK™
Notes
68-0312—06