VISIONPRO
8000 WITH REDLINK™
Installing Wallplate
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
NOTE: For best RedLINK performance, mount thermo-
stats at least 2 feet apart.
The thermostat can be mounted horizontally on the wall or
on a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.
1. Press button on top and pull to remove the wallplate.
Fig. 15. Separate wallplate from thermostat.
2. Position and level the wallplate (for appearance only).
3. Use a pencil to mark the mounting holes.
4. Remove the wallplate from the wall and, if drywall,
drill two 3/16-in. holes in the wall, as marked. For
firmer material such as plaster, drill two 7/32-in.
holes. Gently tap anchors (provided) into the drilled
holes until flush with the wall.
5. Position the wallplate over the holes, pulling wires
through the wiring opening. See Fig. 16.
6. Insert the mounting screws into the holes and
tighten.
Fig. 16. Mounting wallplate.
68-0312—06
C
S1
S1
K
S1
S1
R
C
W
O/B
R
Y
Y
U1
G
G
U1
W2
AUX
-E
U2
Y2
Y2
U2
L/A
A
Installing VisionPRO® 8000 with
RedLINK™
Connect Power
1. Insert supplied AA alkaline batteries for primary or
backup power.
Fig. 17. Insert AA batteries.
NOTE: When the thermostat is NOT used with the Equip-
ment Interface Module or the TrueZONE Wireless
Adapter, a C wire is required for RedLINK.
2. For 24VAC primary power, connect common side of
transformer to C terminal.
CONVENTIONAL
C
K
RC
R
U1
U1
U2
U2
Fig. 18. Connecting C wire to terminal block.
Wiring the Thermostat
IF THE THERMOSTAT IS WIRED DIRECTLY TO THE
EQUIPMENT
1. Refer to Fig. 19. See Table 11 on page 119 for termi-
nal designations and "Wiring" beginning on
page 118 for more information.
2. Turn on 24VAC NOW.
NOTE: 24VAC (C wire) is required to connect
RedLINK accessories.
12
S1
S1
S1
S1
W
O/B
Y
Y
G
G
W2
AUX
-E
Y2
Y2
A
L/A
HEAT PUMP