Installer Tests; Accessing Installer Tests; Using The Equipment Test - Honeywell Home VisionPRO 8000 Manual

With redlink
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH REDLINK™

INSTALLER TESTS

Use the installer tests to check out the system:
• Equipment Test: Tests the heating, cooling, fan, and IAQ
equipment. The test allows you to manually call for each
system to ensure the equipment and thermostat operate
properly. Any minimum off timers are ignored during the
system test. You can test the following equipment:
Heat
Em Heat
Cool
Fan
Humidification
Dehumidification
Ventilation
Economizer
Time of Day
• Wireless Test: Run this test to verify that the thermostat
can communicate properly in the installed location. The
test measures the signal strength between the
Thermostat and the Equipment Interface Module
(in non-zoned applications)
Thermostat and the TrueZONE Wireless Adapter (in
zoned applications)

Accessing Installer Tests

1. Press MENU on the home screen, then scroll down to
Installer Options and press SELECT.
2. Enter the password (date code) when prompted. See
"Finding Your Password (Date Code) to Access
Installer Options" beginning on page 20 for more
information.
3. Scroll down to Installer Test and press SELECT.
Fig. 64.
4. Select Equipment Test or Wireless Test.
Fig. 65.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed during
the Equipment Test
Avoid cycling compressor quickly.
68-0312—06

Using the Equipment Test

1. Select the equipment you want to test and press the
arrow buttons to turn the equipment on/off. Press
Back to test the remaining equipment.
NOTE: The time out for the Equipment Test mode is
30 minutes (if there is no keypress for 30
minutes, the thermostat will automatically
exit the Equipment Test).
2. Run Time, Discharge, Return and Delta T data are dis-
played for heating and cooling tests (requires Dis-
charge and Return Air Sensors). See Fig. 68.
The Discharge, Return and Delta T are updated every
30 seconds during the test. The Run Time counter
starts over when the next stage is turned on.
56
Fig. 66.
Fig. 67.
Fig. 68.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Yth8321r1002Th8110r1008Th8321r1001Th8320r1003

Table of Contents