Honeywell Home VisionPRO 8000 Manual page 49

With redlink
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
User Humidifier in Heat Mode - No
806
User Humidifier in
or Yes
Heat Mode
Use Humidifier in Cool Mode - No
Use Humidifier in
or Yes
Cool Mode
Use Humidifier in Off Mode - No
or Yes
Use Humidifier in
Off Mode
Hum when Heat is On
807
Humidifier Control
Hum when Fan is On
Tstat Controls Fan
Hum Controls Fan
Yes
808
Run Humidifier
when Cool is On
No
Off
810
Hum Tank / Filter
Reminder
60 Run Time Days
90 Run Time Days
6 Calendar Months
12 Calendar Months
Off
810
Humidifier Pad
60 Run Time Days
Reminder
90 Run Time Days
6 Calendar Months
12 Calendar Months
Residential:
900
Dehumidification
Equipment
None
A/C with Low Fan
A/C with High Fan
Dehumidifier
Commercial:
None
A/C with Low Fan
A/C with High Fan
Hot Gas Bypass
Dehumidifier
Table 3. Installer Setup (ISU) Table. (Continued)
Settings
Default
User Humidifier
in Heat Mode -
Yes
Default varies
based on
heating/cooling
equipment
selected
Defaults to Hum
when Heat is On
when ISU 800
Humidifier Type
is Bypass or Fan
Pwrd
Defaults to
Tstat Controls
Fan when ISU
800 Humidifier
Type is Steam
Yes
Off
Off
None
49
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Both
No
Heat: Includes Heat, Emergency Heat and Auto. If
the system is in Auto mode, the thermostat will
allow humidification if the last call was for heat.
Cool: Includes Cool and Auto. If the system is in
Auto mode, the thermostat will allow
humidification if the last call was for cool. A
discharge air temperature sensor is required to
humidify in the Cool mode.
Off: The thermostat will allow humidification when
the system setting is Off.
See "Set up Humidification" beginning on
page 81.
Both
No
Hum when Heat is On: The thermostat turns on the
humidifier only if the heat is currently running and
humidification is needed.
Hum when Fan is On: The thermostat turns on the
humidifier only if the fan is currently running and
humidification is needed.
Tstat Controls Fan: The thermostat turns on the
humidifier and the fan when humidification is
needed.
Hum Controls Fan: The thermostat turns on the
humidifier when humidification is needed and the
humidifier controls the fan.
Both
No
Yes: Humidifier can run when the cooling system is
on.
No: Humidifier can NOT run when the cooling
system is on.
Both
No
This ISU is only displayed if ISU 800 Humidifier
Type is Steam.
Run Time Days are not shown if ISU 800
Humidifier Type is set to None.
Both
No
This ISU is only displayed if ISU 800 Humidifier
Type is Bypass or Fan Pwrd.
Run Time Days are not shown if ISU 800
Humidifier Type is set to None.
Both
No
See "Dehumidification - Residential" beginning on
page 83 or "Dehumidification - Commercial"
beginning on page 88.
®
8000 WITH REDLINK™
Notes
68-0312—06