ISU
Installer Setup
Number
Name
None
509
Discharge Sensor
S1
S2
S3
S4
10K
510
Discharge Sensor
Type
20K
Off
511
A-Coil Low Temp.
Cutoff
35° F to 65° F (in 5° F increments)
No
600
Dry Contact Device
on S Terminals
Yes
No
600
Remote Setback Dry
Yes
Contact
No
600
Full Drain Pan Dry
Yes
Contact Alert
No
600
Dirty Filter Dry
Contact Alert
Yes
No
600
Water Leak Dry
Contact Alert
Yes
No
600
Sys. Shutdown Dry
Yes
Contact Alert
No
600
Service Needed Dry
Contact Alert
Yes
Table 3. Installer Setup (ISU) Table. (Continued)
Settings
Default
None
10K
Off
No
No
No
No
No
No
No
43
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Both
No
Select the terminals wired to the Discharge Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and S4
Both
No
Select 10K or 20K based on the sensor installed.
Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
Both
No
If an optional Discharge Sensor is used, this
feature can help prevent icing on the air
conditioning A-Coil.
When temperature reaches the limit you set,
compressor(s) will shutoff while the system fan
continues to run, until the temperature rises to a
safe level.
Both
Yes
Dry Contact Alerts and Remote Setback require an
Equipment Interface Module. This ISU is only
displayed if an S1-S4 terminal is available.
See "Dry Contact Alerts" beginning on page 74
and "Remote Setback (Commercial Use)"
beginning on page 107.
Commercial
Yes
Remote Setback requires an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
Both
Yes
Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See "Dry Contact Alerts" beginning on page 74.
Both
Yes
Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See "Dry Contact Alerts" beginning on page 74.
Both
Yes
Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See "Dry Contact Alerts" beginning on page 74.
Both
Yes
Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See "Dry Contact Alerts" beginning on page 74.
Both
Yes
Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See "Dry Contact Alerts" beginning on page 74.
®
8000 WITH REDLINK™
Notes