VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
No
500
Wired Discharge
Sensor
Yes
[Select Indoor Sensor Name]
501
Indoor Sensor
Name
None
502
Indoor Sensor
S1
S2
S3
S4
10K
503
Indoor Sensor Type
20K
Use [T-Stat Sensor]
Use T-Stat Sensor for Temp Ctrl -
504
for Temp Ctrl
Yes or No
Use [Remote Indoor
Use [Remote Indoor Sensor
Sensor Name] for
Name] for Temp Ctrl - Yes or No
Temp Ctrl
Use T-Stat Sensor in Temp Avg -
Use [T-Stat Sensor]
Yes or No
in Temp Avg
Use [Remote Indoor Sensor
Use [Remote Indoor
Name] in Temp Avg - Yes or No
Sensor Name] in
(Up to 6 Remote Indoor Sensors)
Temp Avg
None
505
Outdoor Sensor
S1
S2
S3
S4
None
507
Return Sensor
S1
S2
S3
S4
10K
508
Return Sensor Type
20K
68-0312—06
Table 3. Installer Setup (ISU) Table. (Continued)
Settings
Default
No
Indoor Sensor
None
10K:
if ISU 101
Application is
Residential
20K:
if ISU 101:
Application is
Commercial
Sensors are
Averaged (T-Stat
Sensor and
Remote)
None
None
10K
Residential,
Commercial
Requires
or Both
EIM
Both
No
Both
No
Both
No
Both
No
Both
No
Both
No
Both
Yes
Both
Yes
42
Notes
The thermostat will not display the Wired
Discharge Sensor option if there is no fan in the
system.
Select a name (location) of the Wired Remote
Indoor Sensor.
Select the terminals wired to the Remote Indoor
Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and S4
Select 10K or 20K based on the sensor installed.
Refer to resistance values below:
C7189U1005 = 10K ohm
C7772 = 20K ohm
TR21 = 20K ohm
TR21-A = 10K ohm (IMPORTANT - the TR21-A
must be used in combination with a TR21 sensor
or another TR21-A sensor for the thermostat to
calculate the correct indoor temperature reading).
See "Wiring guide — Wired Indoor Sensors"
beginning on page 137 for information on the
sensor type you should select based on how the
sensors are wired. For example, you would select
20K when you have two TR21-A (10K) sensors
wired in series.
Select the sensors to be used for temperature
control. If you select more than one, the
thermostat will average the temperature readings
from each sensor.
See "Remote Indoor Sensors" beginning on
page 113.
Select the terminals wired to the Outdoor Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and S4
Select the terminals wired to the Return Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and S4
Select 10K or 20K based on the sensor installed.
Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm