ISU
Installer Setup
Number
Name
No
215
Run Backup Heat
Yes
with Primary
Equip Controls Fan
216
Backup Heat Fan
Tstat Controls Fan
None
217
Backup Heat Stage
2
U1
Electric
218
Backup Heat Type
Gas/Oil
No
219
External Fossil Fuel
Yes
Kit
No
222
Economizer fault
Yes
"FDD"
Thermostat terminal U1
222
Economizer Wiring
Table 3. Installer Setup (ISU) Table. (Continued)
Settings
Default
No
Tstat Controls
Fan
Default varies
based on
previous
selections
Electric
No
No
Thermostat
terminal U1
25
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Both
No
This ISU is only displayed when ISU 201 Heating
Equipment is Other.
When ISU 201 Heating Equipment is Other, you
can select how the Backup Heat operates. The
thermostat can be setup to keep the primary heat
source on when it calls for Backup Heat or the
thermostat can be setup to turn off the primary
heat source when it calls for Backup Heat.
When ISU 201 Heating Equipment is Radiant
Heat, the thermostat keeps the Radiant Heat on
when it calls for Backup Heat.
Both
No
This ISU is only displayed for conventional systems
when ISU 212 Backup Heat Type is Electric.
Backup Heat Fan Operation automatically defaults
to Equip Controls Fan when ISU 212 Backup Heat
Type is Gas/Oil.
Both
No
TH8321 Thermostat Only:
This ISU is only displayed on the TH8321
thermostat when it is wired directly to the
equipment (Equipment Interface Module is NOT
used).
The thermostat can support up to 2 backup heat
stages for heat pump applications. When there are
2 backup heat stages, backup heat stage 2 must
be wired to U1.
U1 is a normally open dry contact when
configured for a stage of Heat. U1 requires power
from a system transformer or a separate
transformer.
Both
No
This ISU is only displayed when ISU 201 Heating
Equipment is Air to Air Heat Pump, Geothermal or
Geothermal Radiant and there is at least one stage
of backup heat.
See "Heat Pump and Backup Heat Operation"
beginning on page 78.
Both
No
This ISU is only displayed when ISU 201 Heating
Equipment is Air to Air Heat Pump, Geothermal or
Geothermal Radiant and ISU 218 Backup Heat
Type is Gas/Oil.
Commercial
TH8321R
If using a TH8321R without EIM and your code
with no
requires that the thermostat display an alert when
EIM only
the economizer is sending a fault code, select
"Yes". When this is done, the economizer will need
to be wired as shown in Fig. 339 on page 133. If
EIM used, and economizer fault required, this
option is not available. See Fig. 340 on page 133
Commercial
TH8321R
Only shown if "economizer fault FDD" is set to yes.
with no
This setting is to inform installer only. It is not
EIM only
adjustable. See Fig. 339 on page 133.
®
8000 WITH REDLINK™
Notes
68-0312—06