VISIONPRO
8000 WITH REDLINK™
6. If you are creating a custom alert, type the alert name
and press Done. The alert name is what appears on
the Home screen when the alert is detected. See
Fig. 161. You can edit or confirm the alert name after
you enter it.
Fig. 161.
7. Type the custom alert message and press Done. The
custom alert message appears after selecting the
alert and pressing "View More Info". See Fig. 162. You
can edit or confirm the alert message after you enter
it.
Fig. 162.
8. Repeat steps 4–5 for the other Dry Contact, if neces-
sary.

Staging Control

Differential Between All Stages
The thermostat provides Differential settings between all
stages. The equipment changes stages based on how far
the indoor temperature is from the setpoint. Differential
settings provide a way to balance comfort and
conservation.
68-0312—06
Scroll to see:
Contact your
dealer to service
your sump pump
Heat Differential
The indoor temperature must drop to the selected
differential setting before the thermostat will turn on the
stage of heating. For example, if stage 2 is set to 2 °F (1.0
°C), the indoor temperature must be 2 °F (1.0 °C) away
from the setpoint before stage 2 turns on. When set to
Comfort, the thermostat will use the stage of heating as
needed to keep the indoor temperature within 1 °F (0.5 °C)
degree of the setpoint. The thermostat turns on stage 2
when the capacity on stage 1 reaches 90%.
Cool Differential
The indoor temperature must rise to the selected
differential setting before the thermostat turns on the
stage of cooling. For example, if stage 2 is set to 2 °F (1.0
°C), the indoor temperature must be 2 °F (1.0 °C) away
from the setpoint before stage 2 turns on. When set to
Comfort, the thermostat uses the stage of cooling as
needed to keep the indoor temperature within 1 °F (0.5 °C)
degree of the setpoint. The thermostat turns on stage 2
when the capacity on stage 1 reaches 90%.
TO CHANGE DIFFERENTIAL SETTINGS
1. Select Advanced Options to view/adjust differentials
between all stages.
2. Default is Comfort. Adjust differentials as needed.
76
Fig. 163.