VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
None
222
A-L/A Terminal
Time Of Day
Economizer
Heat Pump Fault
Econ. Fault input
Economizer fault
222
A-L/A terminal
Manual
300
System Changeover
Automatic
68-0312—06
Table 3. Installer Setup (ISU) Table. (Continued)
Settings
Default
None
or
Econ. Fault input
Manual:
if ISU 101 is
Residential
Automatic:
if ISU 101 is
Commercial
Residential,
Commercial
Requires
or Both
EIM
Commercial
No
"Econ.
Fault
input" for
TH8321R
with no
EIM only
Commercial
"Econ.
Fault
input" for
TH8321R
with no
EIM only
Both
No
26
Notes
This ISU is only displayed when ISU 101
Application is Commercial.
Note: When the thermostat is setup for Residential,
the L/A terminal operates as described under
"Heat Pump Fault". The L/A terminal requires no
setup for residential applications.
None: The A-L/A terminal is not used.
Time of Day: The A-L/A terminal is energized
during Occupied periods and when the user
overrides the temperature. The terminal is de-
energized during Unoccupied periods and in
Standby mode.
Economizer: The thermostat controls an
economizer module to provide ventilation during
Occupied periods and free cooling when outdoor
conditions are favorable. The
A-L/A terminal is energized during Occupied
periods and during a call for cooling in
Unoccupied periods. See "Economizer and Time of
Day (TOD) Operation" beginning on page 108.
Notes: The economizer module determines when
outdoor conditions are favorable for free cooling.
Heat Pump Fault: When 24 volts is detected on the
L/A terminal (compressor monitor), the thermostat
displays a message to alert the user when the heat
pump requires service. The L/A terminal sends a
continuous output to a zone panel when the
thermostat is set to Emergency Heat mode. The
zone panel will not turn on the heat pump when a
zone is set to Emergency Heat mode.
Econ. Fault input: Only shown if "Economizer fault
FDD" is set to "yes". Not adjustable.
This ISU is only shown when the "Economizer fault
FDD" is set to "yes". It is set for "economizer fault"
and is not adjustable. It is meant to inform the
installer that the A-L/A terminal needs to be wired
to the economizer as shown in Fig. 339 on page
133.
Manual: The user must select heating or cooling as
needed to maintain the desired indoor
temperature.
Automatic: The user has the option to select Auto
for the system setting. In Auto mode, the
thermostat controls heating and cooling
equipment as needed to maintain the desired
indoor temperature.