Minimum On Time (ISU 908 and 909): This option ensures
that the compressor runs long enough to effectively reduce
humidity when the cooling equipment is cycled on. The
compressor will run for the minimum "on time" you set until
the desired humidity level is reached.
Cooling Droop (ISU 908 and 910): This option uses the
cooling system to lower the temperature up to 5° F below
the current cool setpoint until the desired humidity is
reached. The Dehum Over Cooling Limit range is from 1° to
5° F.
Cooling Droop with Minimum On Time (ISU 908, 909, and
910): This method uses both options above to reduce
humidity while maintaining a comfortable temperature.
Reheat (ISU 908): This option allows heating to run during
dehumidification to help maintain a comfortable
temperature. If only cooling stage 1 is used, during the "off"
cycle, both cooling and heating run at the same time as
needed to dehumidify without overcooling. This option
cannot be used in the Heat mode. This option is effective
only if using a system with the A-Coil located before the
heating coil (heat exchanger). This feature requires a
conventional forced air heating system (gas, oil, or electric)
in the application.
NOTE: Reheat can be used on heat pump applications
that have a forced air backup heat source (gas, oil,
or electric). The thermostat will turn on the first
stage of forced air backup heat during Reheat.
NOTE: Reheat can be used on systems where the A-Coil is
located after the heating coil (heat exchanger), but
it is not effective at removing humidity.
Reheat with Minimum On Time (ISU 908 and 909): This
method uses both Reheat and Minimum On Time options
above to reach the desired humidity level.
If set for A/C with Low Speed Fan, configure U1, U2, or U3
as normally open or normally closed (ISU 905) and wire to
the Low Speed Fan terminal on the equipment. For
example, if the U1, U2, or U3 terminal is normally closed, it
will open when the thermostat calls for
dehumidification.See "Wiring IAQ Equipment or a
Heat/Cool Stage to the U Terminals" beginning on
page 130.
NOTE: The thermostat will not lower the fan speed when
the second stage of cooling is on.
Set up Dehumidification With Cooling
System
Some screens shown in this section may not appear on the
thermostat, depending on how you set up
dehumidification.
1. Select the Dehumidification Equipment in ISU 900.
See Fig. 210.
2. If optional remote wireless indoor sensors are
installed, you can choose which sensor you want to
use for dehumidification control. For example, you
can use one sensor for humidification control, and
another for dehumidification. See "Wireless Indoor
Sensor" beginning on page 114 for more informa-
tion.
3. If you are sensing humidity from two separate loca-
tions (one for humidification and another for dehu-
midification), you can select which humidity reading
to display on the home screen. See "Wireless Indoor
Sensor" beginning on page 114 for more informa-
tion.
89
®
VISIONPRO
8000 WITH REDLINK™
Fig. 210.
Fig. 211.
Fig. 212.
68-0312—06