Installing Discharge And Return Air Temperature Sensors; Selecting Thermostat Location - Honeywell Home VisionPRO 8000 Manual

With redlink
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

VENTILATOR
OR
DEHUMIDIFIER
MOUNT RETURN
SENSOR HERE
MOUNT DOWNSTREAM
OF BYPASS HUMIDIFIER,
DEHUMIDIFIER OR
VENTILATOR
Fig. 11.
BYPASS
HUMIDIFIER
VENTILATOR
OR
DEHUMIDIFIER
MOUNT RETURN
SENSOR HERE
MOUNT DOWNSTREAM
OF BYPASS HUMIDIFIER,
DEHUMIDIFIER OR
VENTILATOR
Fig. 12.
Installing Discharge and Return Air
Temperature Sensors
Use the following steps to mount the Discharge/Return Air
Sensors:
1. Attach plastic cover to the sensor probe.
2. Drill 1/4-inch hole for the sensor probe and mount it
to the ductwork with enclosed screws (see Fig. 13).
MOUNT
DISCHARGE
BYPASS
SENSOR HERE
HUMIDIFIER
MOUNT
DOWNSTREAM
OF BYPASS
HUMIDIFIER
HEAT
EXCHANGER
BLOWER
M33078A
MOUNT
DISCHARGE
SENSOR HERE
HEAT
EXCHANGER
BLOWER
M33079A
3. Connect wires to S1, S2, S3 or S4 terminals at the
EIM.
4. Setup the S1, S2, S3 or S4 terminals in the Installer
Setup at the thermostat.
Fig. 13. Mounting Discharge/Return Air Sensor.

Selecting Thermostat Location

Install the thermostat about 5 ft. (1.5m) above the floor in an
area with good air circulation at average temperature. See
Fig. 14.
NO
NO
[1.5 METERS]
Fig. 14. Selecting thermostat location.
Do not install the thermostat where it can be affected by:
— Drafts or dead spots behind doors and in corners.
— Hot or cold air from ducts.
— Radiant heat from sun or appliances.
— Concealed pipes and chimneys.
— Unheated (uncooled) areas such as an outside wall
behind the thermostat.
11
®
VISIONPRO
8000 WITH REDLINK™
M32995
NO
YES
5 FEET
M19925
68-0312—06