Honeywell Home VisionPRO 8000 Manual page 44

With redlink
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
No
600
Fan Failure Dry
Contact Alert
Yes
No
600
Custom Dry Contact
Alert
Yes
None
601
Remote Setback
S1
S2
S3
S4
N.O. when Occupied
602
Remote Setback is
[See Settings]
N.C. when Occupied
0 to 30 minutes (in 5 minute
603
Remote Setback
increments)
Time Delay
72° F to 90° F
604
Remote Setback
Cool Setpoint
68-0312—06
Table 3. Installer Setup (ISU) Table. (Continued)
Settings
Default
No
No
None
N.O. when
Occupied
0 minutes
85° F
Residential,
Commercial
Requires
or Both
EIM
Both
Yes
Both
Yes
Commercial
Yes
Commercial
Yes
Commercial
Yes
Commercial
Yes
44
Notes
Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See "Dry Contact Alerts" beginning on page 74.
Dry Contact Alerts require an Equipment Interface
Module. This ISU is only displayed if an S1-S4
terminal is available.
See "Dry Contact Alerts" beginning on page 74.
Remote Setback requires an Equipment Interface
Module.
Select the terminals wired to the Remote Setback
Dry Contact Device.
Remote Setback requires an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open when Occupied: The Dry Contact
device is open when the room is occupied and will
close when the room is unoccupied.
Normally Closed when Occupied: The Dry Contact
device is closed when the room is occupied and will
open when the room is unoccupied.
Remote Setback requires an EIM (Equipment
Interface Module).
The Remote Setback Time Delay forces the
thermostat to wait before it switches from
Occupied to the Remote Setback temperature
settings.
When set to 0 minutes, the thermostat will switch
from Occupied to the Remote Setback
temperature settings immediately when the room
is unoccupied.
Remote Setback requires an EIM (Equipment
Interface Module).
During occupied periods, the occupancy sensor
tells the thermostat to go to setback settings when
no one is in the room. If someone is in the room,
then it follows the settings of the occupied period.
The occupancy sensor is ignored during
unoccupied periods.
If the thermostat is setup for non-programmable,
the occupancy sensor tells the thermostat to go to
setback settings when no one is in the room. If
someone is in the room, then it follows the settings
set by the user.