Honeywell Home VisionPRO 8000 Manual page 27

With redlink
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
2° F to 9° F (in 1° F increments)
300
Auto Changeover
Deadband
Basic Options
301
Control Options
Advanced Options
No
302
Finish With High
Yes
Cool Stage
No
302
Finish With High
Yes
Heat Stage
Table 3. Installer Setup (ISU) Table. (Continued)
Settings
Default
3° F
Basic Options
No
No
27
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Both
No
This ISU is only displayed when ISU 300 is set to
Automatic.
Deadband is the minimum separation between
heat and cool settings when the thermostat is
setup for Auto Changeover. For example, if the
deadband is set to 3° F and the cool setpoint is 75°
F, the warmest heat setpoint allowed would be 72°
F. If the heat setpoint is adjusted above 72° F, it
will automatically adjust the cooling setpoint
higher to maintain the 3° F deadband.
When ISU 907 or ISU 910 (Dehum Over Cooling
Limit) is set to 1, 2, 3, 4 or 5 F, the thermostat will
not show the full Deadband range. For example, if
you set a Deadband of 3 F and an Over Cooling
Limit of 2 F, the minimum Deadband that you can
select will be 5 F. This prevents the heating system
from turning on when the thermostat over cools to
reach the dehumidification setting.
Both
No
Basic Options: The Installer Setup displays basic
temperature control options which include Backup
Heat Droop, Backup Heat Upstage Timer, Outdoor
Temperature Lockouts and Cycle Rate settings per
stage.
Note: Outdoor Temperature Lockouts only apply to
Heat Pump applications.
Advanced Options: The Installer Setup displays
both Basic and Advanced Options. Advanced
temperature control options include Finish With
High Cool Stage, Finish With High Heat Stage, and
Temperature Differential settings between all
stages.
Both
No
ISU 301 Control Options must be set to Advanced
to view or adjust Finish With High Cool Stage.
This ISU is only displayed when the thermostat is
set for 2 or more cool stages.
When set to Yes, this feature keeps the high stage
of the cooling equipment running until the desired
setpoint is reached.
Both
No
ISU 301 Control Options must be set to Advanced
to view or adjust Finish With High Heat Stage.
This ISU is only displayed when the thermostat is
set for 2 or more heat stages.
When set to Yes, this feature keeps the high stage
of the heating equipment running until the desired
setpoint is reached.
®
8000 WITH REDLINK™
Notes