Backup Control

This section explains when backup control is used. For
example, if batteries in the wireless indoor sensors are
depleted.
If the Thermostat is Part of the
Temperature Average
1. The thermostat controls the system using the
remaining sensors that are part of the temperature
average.
2. If there are no remote indoor sensors remaining, the
thermostat controls the system using its internal
sensor.
3. If the internal thermostat sensor is not available and
a Return Air Sensor is connected, the Backup Control
in the EIM is used. The backup control maintains
55 °F in heat, 85 °F in cool and operates the fan con-
tinuously to sense and control temperature.
If the Thermostat is NOT Part of the
Temperature Average
1. The thermostat controls the system using the
remaining sensors that are part of the temperature
average.
2. If there are no remote indoor sensors remaining and
a Return Air Sensor is connected, the Backup Control
in the EIM is used. The backup control maintains
55 °F in heat, 85 °F in cool and operates the fan con-
tinuously to sense and control temperature.

REPLACING A THERMOSTAT

When you replace a thermostat, you must reset the
RedLINK accessories before connecting them to the new
thermostat.
Follow the instructions below:
At the Equipment Interface Module (EIM)
1. Press and hold the CONNECT button on the EIM until
the CONNECTED LED glows amber (hold for about
10 seconds).
2. Follow the prompts on the screen to connect the new
thermostat to the EIM. See page 15.
At the Portable Comfort Control
1. Press and hold the blank space (or arrow) in the lower
right hand corner of the screen until the display
changes (hold for about 4 seconds).
2. Press REMOVE, then YES to disconnect from the old
thermostats.
3. To reconnect the thermostat, go to "Linking RedLINK
Accessories" beginning on page 15.
At the Indoor Sensor, RedLINK Internet
Gateway, Entry/Exit Remote, Vent-Filter
Boost Remote or TrueSTEAM Wireless
Adapter
1. Press and hold the CONNECT button on the acces-
sory until the status light glows amber (hold for about
10 seconds).
2. To reconnect the thermostat, go to "Linking RedLINK
Accessories" beginning on page 15.
REPLACING AN EQUIPMENT
INTERFACE MODULE
When you replace an EIM, you must reset the RedLINK
accessories before connecting them to the new thermostat.
Follow the instructions below:
At the thermostat
1. Press MENU, scroll down and select Installer Options,
enter the password (Date Code) when prompted,
scroll down and select Wireless Manager, scroll down
and select Remove Device, then select This Thermo-
stat.
2. Follow the prompts on the screen to connect the
thermostat to the new EIM.
At the Portable Comfort Control
1. Press and hold the blank space (or arrow) in the lower
right hand corner of the screen until the display
changes (hold for about 4 seconds). See Fig. 311.
2. Press REMOVE, then YES to disconnect from the old
thermostats. To reconnect the thermostat, go to
"Linking RedLINK Accessories" beginning on