INSTALLER SETUP NUMBERS, SETTINGS, AND TESTS
(TABLE 4)

Configure Installer Setup

1. Press and release the System key.
2. Press System and Done keys simultaneously.
3. Hold keys for approximately five seconds, until
the screen changes.
4. When the display changes, release the System
and Done keys.
NOTE: See Table 4 for installer setup (ISU) numbers
and settings.

Installer System Tests

Use the Installer System Test section to test the
heating, cooling and fan. Refer to the latter portion of
Table 4.
Installer
Setup
Installer Setup
Number
Name
0120
Date (Year Upper) 20
0130
Date (Year Lower) 08
0140
Date (Month)
0150
Date (Day)
0160
Schedule Options 4
0170
System Selection
0180
Heat Fan
Operation
0185
Pre-occupancy
Purge Duration
0190
Reversing Valve
O/B
0220
Cycles Per Hour
(CPH) for first
stage cooling/
compressor
0240
CPH for first stage
heat
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
Table 4. Installer Setup Menu.
Default
Setting
All Settings
20—21
00-99
6
1-12
15
1-31 (Month
Dependent)
0—Non-Programmable
4—Programmable
1
1—1H/1C Conv
2—1H w/o fan
3—1H with fan
4—1C
5—1H/1C HP
6—2H/1C HP
7—4 pipe Fan Coil
8—2 pipe Fan Coil
9—2 pipe Fan Coil w/
Aux Heat
10—PTAC 1H/1C (Hi
speed, Lo speed Fan)
11—PTAC 2H/1C (Hi
speed, Lo speed Fan)
0
0—Fossil
1—Electric
0
0—no duration
1—one hour
2—two hours
3—three hours
0
0—O (O/B On Cool)
1—B (O/B On Heat)
3
1-6
5
1-12
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed
during Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cool-
ing and fan. The setting chosen for System
Type (Installer Setup Number 0170) can pre-
vent some System Test Numbers from appear-
ing.
Available year range: 2001 - 2178
Available year range: 2001 - 2178
Relay Y is used for 2 pipe fan coil output relay.
Only shows up if conventional system with
heat stages and fan capability is selected
(ISU 0170). If heat pump is selected, fan
defaults to electric. If fan coil or PTAC modes
are selected, fan defaults to electric (does not
show up).
Shown only if system has fan and schedule is
programmable (ISU 0160).
Pre-occupancy purge is enabled by a
nonzero duration.
Only shown if heat pump or PTAC system is
selected.
Only shown if system has cool stages (ISU
0170). Shown for heat pump, fan coil, PTAC,
and conventional cooling stages.
Only shown if system is conventional with
heat stages, 4 pipe fan coil, 2 pipe fan coil
(ISU 0170).
9
Notes
62-0273—07