INSTALLER MENU
To enter the Installer menu  press the      button
and then      until the display changes (approx. after 3 secs)
Specific Applications
Heating
Gas Boilers
(30kW)
Oil Boiler
Thermal 
Actuator
Zone valve
Special Features
Opentherm®
Heat range
Schedule options
External temperature 
sensor (only for wired 
versions)
Optimisation (optimum 
start, optimum stop and 
delayed start)
Clock setting
Temperature offset
Binding (only for T4R)
Reset
Failsafe
Setting
CpH
Minimum on 
(cycle per hour)
6
3
12
6
Description
By connecting the T3M to an OpenTherm® appliance various specific data can be viewed. The 
data is depending on what the appliance is providing.
The normal lower temperature limit of 5 °C can be increased up to 21 °C
to protect the inhabitants from cold. Useful if the inhabitants include the elderly, children or 
disabled. The normal upper temperature limit of 37 °C
can be reduced down to 21 °C to save the homeowner energy. Useful if the homeowner rents 
to tenants.
The thermostat has the 7 days by default, however it can be change to 7 days for different 
schedule each day of the week or 1 day for having the same schedule during the week
An external temperature sensor can be fitted, allowing the thermostat to control the 
temperature from another room or space, where it is inconvenient to locate the thermostat. 
It will read the remote sensor every 1 minute. The sensor can be connected up to 50 meters 
from the unit. Useful for commercial premises where the public may tamper with the product
Optimum Start: learns how long it takes your system to reach the temperature you want. It 
turns on the heating system earlier to make sure it's comfortable at the scheduled time.
Optimum Stop: Saves energy and money by switching off a little bit earlier than the normal 
programmed time. If the home is up to temperature, it will not notice the effect on the 
temperature, but will show a difference in the fuel bill.
Delayed start: Saves energy by slightly delaying the start of heating depending on the 
difference between the scheduled temperature and the actual room temperature.
Change display format (default 24hr) and adjust time and date.
If the Thermostat is located in a hot/cold location and cannot be moved because of wiring 
then the measured/ displayed temperature can be adjusted by +/‐ 3 °C. Useful if the 
homeowner wants the reading to match another appliance temperature display.
Menu to bind the Thermostat and the Receiver box, test the RF signal strength of the radio 
communication and to clear an existing binding.
Reset the thermostat back to factory default settings, reset the schedule to default.
When the temperature sensor fails(T3,T3M) or the radio communication between the 
Thermostat and the Receiver box is lost the device will cycle the demand 20% On / 80% Off
T3 PROGRAMMABLE THERMOSTAT 
What do you need to change?
Note:
Time (min)
a.
To change cycle per hour
b. To change minimum ON time
1
No action required
4
a.
Set minimum ON time to 4 minutes.
b. Set cycle per hour to 3.
1
Set cycle per hour to 12.
1
No actions required