Ai 4-20 Ma + 6-Byte Mailbox; Table 18: Process Values For The Hart Module - WAGO 750-484 Manual

2 ai 4-20 ma hart ex i 2-channel-analog input module 4-20 ma hart, ex i
Hide thumbs Also See for 750-484:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-484 2 AI 4-20 mA HART Ex i
Status information, which can be evaluated in the event of a fault, is contained in
the two least significant bits (B0 and B1). If the measurement is above the
measuring range, Bit B0 is set = 1, and if the measurement is below the measuring
range or if a wire breaks, Bit B0 and B1 are set = 1.
The input voltage range for the measured values of 4 mA to 20 mA is scaled to
the numerical range from 0x0000 to 0x7FFD.

Table 18: Process Values for the HART Module

Input Current
4 mA ... 20 mA
<3
<4
4
6
8
10
12
14
16
18
20
>20
>22
*) Status bits: F = Cable Break, O = Overrun
4.1

2 AI 4-20 mA + 6-Byte Mailbox

In the "2AI + 6-byte mailbox" operating mode the HART module provides the
fieldbus coupler/controller with a 12-byte input and output process image via one
logical channel.
1 control byte (C0) and 1 status byte (S0) are used to monitor the data flow.
The data is mapped in the cyclic process image of the connected
coupler/controller. However, the HART commands can then be implemented by
the "WagoLibHart_0x.lib" PLC library. The data is tunneled to the application via
a mailbox and decoded by means of the library so that evaluation and processing
take place directly at the application level.
The IEC application can be implemented in the connected programmable fieldbus
controller (PFC) of the fieldbus node with the WAGO-I/O-PRO programming
tool or, if a fieldbus coupler is connected, in the superimposed controller.
Manual
V 1.2.0 HW-Version 04, SW-Version 03
Numeric Value
Binary
*)
Measured Value
'0000.0000.0000.00
11'
'0000.0000.0000.00
00'
'0000.0000.0000.00
00'
'0001.0000.0000.00
00'
'0010.0000.0000.00
00'
'0011.0000.0000.00
00'
'0100.0000.0000.00
00'
'0101.0000.0000.00
00'
'0110.0000.0000.00
00'
'0111.0000.0000.00
00'
'0111.1111.1111.11
00'
'0111.1111.1111.11
00'
'0111.1111.1111.11
01'
F O
Hex.
Dec.
0x0003
0x0000
0x0000
0x1000
4096
0x2000
8192
0x3000
12288
0x4000
16384
0x5000
20480
0x6000
24576
0x7000
28672
0x7FFC
32764
0x7FFC
32764
0x7FFD
32765
Process Image
Status
LED
Byte
Error
Hex.
AI 1, 2
3
0x41
on
0
0x00
off
0
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x42
on
31