7. Troubleshooting
C200A24
It took too long to
stabilize 24V IO
C200A25
24V voltage is too
high
C200A26
24V IO voltage is too
high
C201A
Setup of Safety
Control Board failed
C201A0
Setup of Safety
Control Board failed
C201A1
SCB uA is not
responding
C201A2
SCB uB is not
responding
C201A3
SCB is not
responding
C202A
SCE configuration
was illegal, after
applying tolerances
Service Manual
No data was received from
the Control Board at
initialization or invalid
safety parameters have
been received
No data or invalid data was
received from the Control
Board uA at initialization
No data or invalid data was
received from the Control
Board uB at initialization
No data or invalid was
received from Control Board
when requested for
configuration parameters
137
a) Do a Complete rebooting
sequence.
b) Check 24 V and Control
Board for issues
a) Check external 24 V and
Control Board for issues.
b) Do a Complete rebooting
sequence.
c) If this happens more than
two times in a row, replace
Safety Control Board.
a) Disconnect I/O's.
b) Do a Complete rebooting
sequence.
c) Check external 24 V and
Control Board for issues
a) Do a Complete rebooting
sequence
b) Update software
c) Contact your local
Universal Robots service
provider for assistance.
a) Do a Complete rebooting
sequence
b) Update software
c) Contact your local
Universal Robots service
provider for assistance.
Do a Complete rebooting
sequence.
Do a Complete rebooting
sequence.