Process Values; Table 27: Process Values, 0 Ma; Table 28: Process Values, 4 Ma; Table 29: Process Values, 6 V - WAGO 750-563/040-000 Manual

2-channel analog output module; 0/4...20 ma / 6...18 vdc, 16-bit, /xtr for wago-i/o-system 750 xtr
Table of Contents

Advertisement

36
Process Image
4.3

Process Values

Table 27: Process Values, 0 mA ... 20 mA
0 mA ... 20 mA, [I
Table 28: Process Values, 4 mA ... 20 mA
4 mA ... 20 mA, [I
Table 29: Process Values, 6 V ... 18 V
6 V ... 18 V, [U
Manual
Version 1.3.0
750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR
Data Format 0 ... 65535
Manufacturer calibration, without user scaling
] = mA
A
0.0
5.0
10.0
15.0
20.0
Data Format 0 ... 65535
Manufacturer calibration, without user scaling
] = mA
A
4.0
8.0
12.0
16.0
20.0
Data Format 0 ... 65535
Manufacturer calibration, without user scaling
] = V
A
6.0
9.0
12.0
15.0
18.0
WAGO-I/O-SYSTEM 750 XTR
Numeric value
hexadecimal
0000
3FFF
7FFF
BFFF
FFFF
Numeric value
hexadecimal
0000
3FFF
7FFF
BFFF
FFFF
Numeric value
hexadecimal
0000
3FFF
7FFF
BFFF
FFFF
decimal
0
16383
32767
49151
65535
decimal
0
16383
32767
49151
65535
decimal
0
16383
32767
49151
65535

Advertisement

Table of Contents
loading

This manual is also suitable for:

2ao 0/4-20ma/ 6-18v dc/ 16bit /xtr