Table 21: Process Image Of The I/O Module, Examples Of Process Values - WAGO 750-457/040-000 Manual

4ai +/-10v dc s.e. /xtr, 4-channel analog input module, ±10 v, single-ended /xtr for wago-i/o-system 750 xtr series
Table of Contents

Advertisement

34
Process Image
The following table shows examples:

Table 21: Process Image of the I/O Module, Examples of Process Values

Imput
Voltage
±10 V
< −10
−10.0
−8.0
−6.0
−4.0
−2.0
0.0
2.0
4.0
6.0
8.0
10.0
> 10.0
1)
Bit B2: not defined
Bit B1 and bit B0: Indicates if the measuring range is overrange / underrange
Manual
Version 1.3.0
Numeric Value
Binary
Binary
Measured Value
Diagnostics
'1000.0000.0000.0 011'
'1000.0000.0000.0 000'
'1001.1001.1001.1 000'
'1011.0011.0011.0 000'
'1100.1100.1100.1 000'
'1110.0110.0110.0 000'
'0000.0000.0000.0 000'
'0001.1001.1001.1 000'
'0011.0011.0011.0 000'
'0100.1100.1100.1 000'
'0110.0110.0110.0 000'
'0111.1111.1111.1 000'
'0111.1111.1111.1 011'
WAGO-I/O-SYSTEM 750 XTR
750-457/040-000 4AI +/-10V DC S.E. /XTR
Hex.
Dez.
1)
−32.765
0x8003
−32.768
0x8000
−26.216
0x9998
−19.664
0xB330
−13.112
0xCCC8
−6.560
0xE660
0x0000
0
0x1998
6.552
0x3330
13.104
0x4CC8
19.656
0x6660
26.208
0x7FF8
32.760
0x7FFB
32.763
Status
LED
Byte
Error
Hex.
AI 1...4
0x41
ON
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x42
ON