8.3.6.3.1 "Dmx Receive" Operating Parameters; Table 49: Dmx Diagnostics - Diagnostic Bits In Byte D0 Of The Input Data - WAGO 750-652/040-000 Manual

Serial interface rs-232/rs-485 xtr freely configurable, extreme for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-652/040-000 Serial Interface RS-232/RS-485 XTR
Table 49: DMX Diagnostics – Diagnostic Bits in Byte D0 of the Input Data
Bit number Name
7
6
0 ... 5

8.3.6.3.1 "DMX Receive" Operating Parameters

Functional limitations based on different operating conditions!
The "DMX receive" function has been tested under certain operating conditions.
If the I/O module is operated in conditions other than those listed in this section, it
can lead to functional limitations and data loss.
Additional information on using DMX functions is listed in the "DMX_01
Application Note".
The application note is available for download at the
Note the process image size setting!
In "DMX receive" mode, the correct process image size must be set.
To operate the I/O module in DMX Slave mode, the 24-byte process image size
(default) must be used!
Incorrect operating parameters can lead to functional limitations and instable
operation. Operating parameters are listed below that ensure stable operation.
Sender:
Compatible with DMX specification E1.11-2008/USITT DMX512-A
DMX transmission link:
100 m twisted-pair cable, Cat. 5, terminated with 120 Ω terminating resistors
Receiver:
I/O module 750-652/040-000 firmware version 06 or higher
Node configuration:
-
-
-
Value
Packet ID
0
Transmission
0
failure when
receiving
MaxChNum
0
Position 00: 750-881 [Version: SW 01.05.15(07) / HW 07 / FWL 03]
Position 01: 750-652/040-000 [Version: SW 01.02.15(06) / HW 01]
Process image size: 48 Bytes
Position 02: 750-652/040-000 [Version: SW 01.02.15(06) / HW 01]
Process image size: 24 Bytes
Description
... 1
0
: The start code of the received
bin
bin
bin
DMX packet is 0.
1
: The start code of the received
bin
DMX packet is no 0 (alternative start
code or faulty receipt).
... 1
0
: Receipt of a packet within 1.2 s
bin
bin
bin
1
: More than 1.2 s has passed since
bin
receipt of a valid packet.
21
Number of DMX channels actually
dez ...
dez
received