Table 18: Emc - Immunity To Interference - WAGO 750-563/040-000 Manual

2-channel analog output module; 0/4...20 ma / 6...18 vdc, 16-bit, /xtr for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR
The I/O module 750-563/040-000 meets the following EMC standards as these
standards relate to the I/O module:
Table 18: EMC – Immunity to Interference
Standard
Electrostatic Discharge
• EN 61000-4-2
• EN 60255-26
• IEEE C37.90.3
High-frequency Electromagnetic Fields
• EN 61000-4-3
• EN 60255-26
• IEEE C37.90.2
Fast Electrical Transient Disturbances / Burst
• EN 61000-4-4
• EN 60255-26
• IEEE C37.90.1
Surge Voltage / Surge
• EN 61000-4-5
• EN 60255-26
Conducted Disturbances, Induced by High-frequency Fields
• EN 61000-4-6
• EN 60255-26
Magnetic Fields With Electrical Frequencies
• EN 61000-4-8
• EN 60255-26
Pulse-shaped Magnetic Fields
• EN 61000-4-9
Damped Oscillatory Magnetic Fields
• EN 61000-4-10
Voltage Dips, Short-term Interruptions and Voltage Fluctuations
• EN 61000-4-11
• EN 60255-26
Damped Sinusoidal Oscillations
• EN 61000-4-12
Harmonics and Interharmonics
• EN 61000-4-13
Conducted Asymmetric Disturbances
• EN 61000-4-16
Test Value
8 kV (contact discharge)
8 kV (air discharge)
20 V/m (80 MHz ... 1 GHz)
10 V/m (1 GHz ... 3 GHz)
4 kV
1 kV (conductor/conductor)
2 kV (conductor/ground)
10 V (150 kHz ... 80 MHz)
300 A/m continuous / 1000 A/m for 1 s
300 A/m
100 A/m
Standard not applicable
1 kV (conductor/conductor)
2 kV (conductor/ground)
Standard not applicable
30 V continuous
300 V for 1 s
Device Description
Manual
Version 1.3.0
29