Figure 6-40 Removing a multi-functional sensor
Step 2 Disconnect cables from the rear of the multi-functional sensor.
Step 3 Connect the cables to the reserved multi-functional sensor.
Step 4 Align the slot in the rear of the reserved multi-functional sensor with the buckle on the base,
and slide and clamp the multi-functional sensor.
Step 5 Synchronize the parameters of the multi-functional sensor on the ECC800-Pro WebUI.
Step 6 On the WebUI of the ECC800-Pro, choose Monitoring > System > ECC800 > Controls >
Delete device with communication failure, and click Submit.
Step 7 Log in to the ECC800-Pro WebUI, and edit the plan view by adding new devices.
Step 8 Check the parameters and communication status of the multi-functional sensor to ensure
normal communication.
----End

6.4.8 Replacing a Smoke Detector

Smoke detectors can be installed in various scenarios. This section describes how to replace a
smoke detector on the control skylight.
Impact on the System
Smoke cannot be detected.
Preparations
Issue 05 (2020-03-25)
A reserved multi-functional sensor has a base. You can replace the old base if it is damaged or does not
match the buckle of the reserved multi-functional sensor.
Tools: Phillips screwdriver, insulation tape, step ladder (2 m)
Material: smoke detector