5.6 F: Option Settings
u

PROFIBUS-DP Parameters

Parameters F6-30 through F6-32 set the drive to run on a PROFIBUS-DP network.
n
F6-30: PROFIBUS-DP Node Address
Sets the node address of a PROFIBUS-DP option card.
No.
F6-30
n
F6-31: PROFIBUS-DP Clear Mode Selection
Determines the operation when a Clear Mode command is received.
No.
F6-31
Setting 0: Reset
Resets the drive operation (frequency reference, inputs, outputs etc.).
Setting 1: Maintain the Previous State
Returns the drive status to the state prior to receiving the command.
n
F6-32: PROFIBUS-DP Data Format Selection
Selects the data format used for PROFIBUS-DP communication.
No.
F6-32
Setting 0: PPO-type Data Format
Setting 1: Conventional Data Format
Setting 2: PPO (w/bit 0)
Setting 3: PPO Type (Auto Enter)
Setting 4: Conventional (Auto Enter)
Setting 5: PPO (w/bit0, Auto Enter)
Note:
Settings 2 to 5 are available in drive software versions PRG: 8503 and later.
u

CANopen Parameters

Parameters F6-35 and F6-36 set the drive to operate on a CANopen network.
n
F6-35: CANopen Node ID Selection
Selects the node ID of a CANopen option board.
No.
F6-35
n
F6-36: CANopen Communication Speed
Sets the communication speed for a CANopen option card.
No.
F6-36
202
Parameter Name
PROFIBUS-DP Node Address
Parameter Name
PROFIBUS-DP Clear Mode Selection
Parameter Name
PROFIBUS-DP Data Format Selection
Parameter Name
CANopen Node ID Selection
Parameter Name
CANopen Communication Speed
Setting Range
0 to 125
Setting Range
0, 1
Setting Range
0 to 5
Setting Range
0 to 126
Setting Range
0 to 8
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Default
0
Default
0
Default
0
Default
0
Default
6