NT8D06, NT8D21, NT8D29 Power Supply AC

Use this procedure to replace AC power supplies:
NT8D06 PE Power Supply AC
NT8D21 Ringing Generator AC
NT8D29 CE Power Supply AC
Module covers are not hinged; do not let go of the cover. Lift the cover
away from the module and set it out of your work area.
Removing equipment
1
Turn off power to the module power supply:
— If there is a Module Power Distribution Unit (MPDU), set the circuit
breaker(s) on the associated MPDU to OFF (down).
Note: If there are two circuit breakers on the MPDU, the top one is
associated with the module power supply, the bottom one with the
ringing generator (see Figure 13).
— If there is no MPDU, set the switch on the power supply faceplate to
OFF (down).
2
Unhook the locking devices on the power supply. Wait at least 5 minutes,
then pull the power supply out of the card cage.
Power must discharge. Wait five full minutes before you remove the
power supply from the module.
Replacing equipment
WARNING
CAUTION