Nortel Meridian 1 Replacement Manual page 286

Hardware replacement
Table of Contents

Advertisement

Page 286 of 362
553-3001-520 Standard 16.00 April 2000
Replacing equipment
3
Tag and disconnect the cable to the card you are removing.
4
Unhook the locking devices on the card; pull it out of the card cage.
5
Remove the screw that secures the QMM42 Data Cartridge. Gently
unplug the cartridge from the connectors on the component side of the
FDI card.
Installing equipment
1
Plug the data cartridge into the connectors on the component side of the
replacement FDI card. Install the screw that secures the cartridge.
2
Set the ENB/DIS switch to DIS on the replacement card.
3
Set option switches on the replacement card the same as on the card you
removed. If there is a vintage change, be sure to check Circuit Card:
Installation and Testing (553-3001-211) for any differences.
Incorrect switch settings on an FDI card can cause a system failure.
4
Insert the replacement card into the vacated slot and hook the locking
devices.
5
Connect the cable to the replacement card.
6
Set the ENB/DIS switch to ENB on the replacement card.
7
Switch to the active CPU:
LD 35
SCPU
****
8
Test the FDI card:
LD 37
MSI 0
— If there is a problem, an IOD system message is generated and the
red LED lights on the faceplate of the card.