Nortel Meridian 1 Replacement Manual page 163

Hardware replacement
Table of Contents

Advertisement

4
Pull the card out of the IPE module or cabinet and place it into an
antistatic bag away from the work area.
5
Hold the replacement card by the card locking devices and insert it
partially into the card guides in the module.
6
Pull the upper and lower locking devices away from the faceplate on the
card and insert the card firmly into the backplane connector. Press the
card locking devices firmly against the faceplate to latch the card inside
the module. The Remote Carrier Interface card automatically starts the
self-test.
7
Observe the red LED on the front panel during self-test. If it flashes three
times and stays on, it has passed the test. Go to step 8. If it does not flash
three times and then stays on, it has failed the test. Pull the card partially
out of the module and reinsert it firmly into the module. If the problem
persists, troubleshoot or replace the Remote Carrier Interface card.
8
At the. prompt in the LD 32 program, type
Remote Carrier Interface card number, and press the Enter key to enable
the card. If the upper most red LED on the Remote Carrier Interface card
faceplate turns off, the card is functioning correctly and is enabled. The
outcome of self-test will also be indicated by LD 32 on the MMI terminal
connected to the Remote Carrier Interface card. If the LED stays on,
replace the card.
9
Tag the defective card(s) with a description of the problem and prepare
them for shipment to your equipment suppliers' repair depot.