Nortel Meridian 1 Replacement Manual page 115

Hardware replacement
Table of Contents

Advertisement

Figure 10
NT6D52 Rectifier and QBL15 Power/Battery Distribution Box connections
NT0R72 rectifier
TB3
1
– 48 V
48 V return
2
TB4
+ OUT
+ SENS
– SENS
– OUT
DCON
#22 AWG blue (DCON)
#22 AWG red (– SENSE)
#22 AWG black (+ SENSE)
Note 1: All wiring between the rectifier and the QBL15 is contained in the same conduit.
Note 2: Use single cable for 30 m (100 ft) or less, double cable for 30 to 60 m (100 to 200 ft).
Note 3: The terminal function is marked, but the terminal numbers may not be marked.
6
Disconnect the multimeter and follow normal power up procedure to
restore the system to service.
#4 AWG red (note 2)
#4 AWG black
(note 2)
To other
rectifiers
To other
rectifiers
Replacing equipment
QBL15 distribution box
W1
GND POS (+) positive bus
To other rectifiers (note 1)
DISCHARGE
1
2
TB1
TB2
MONITOR
Trip
DCON field
6
wiring kit
Alarm
6
5
3
5
2
4
(note 3)
TB3
6
– SENSE
5
+ SENSE
4
– SENSE
3
+ SENSE
2
– SENSE
1
+ SENSE
Page 115 of 362
CHARGE
3
4
1
2
To other
rectifiers
NT8D46AT cable to
J4 on system monitor
553-3041
Hardware replacement
3