Replacing equipment
553-3001-520 Standard 16.00 April 2000
22 If there are CCED messages generated by the STAT CPU command on
the replacement CP card, set the NORM/MAINT switch to MAINT,
press the reload (MAN RST) button and set the NORM/MAINT switch
back to NORM. (It may take 2 to 4 minutes for memory synchronization
to take place.)
After the HWI0533 message is displayed, test the replacement CP card
from the active CPU:
TEST CPU
If the test results in:
CCED014
On the active CP card set the NORM/MAINT switch to NORM, and
from the active side enter:
TEST CPU
23 Set the NORM/MAINT switch to NORM on the active CP card (if not
already set).
24 Check the status of the CPUs:
STAT CPU
25 Test the CPU.
TEST CPU
26 Check the status of the CNIs:
STAT CNI
27 Switch Cores and exit the program:
SCPU
****
the test causes a cold start on the inactive CPU
"Test failed because unable to enter SPLIT
mode"
to test the CP card
exit LD 135