Nortel Meridian 1 Replacement Manual page 158

Hardware replacement
Table of Contents

Advertisement

Page 158 of 362
553-3001-520 Standard 16.00 April 2000
Replacing equipment
Installing equipment
1
Install the replacement PDU:
a
Connect the frame ground wire from the PDU to the frame ground
bolt inside the pedestal.
b
Guide the connector for the power cable through the hole in the top
of the pedestal (do not allow the PDU to drop).
c
Gently push the PDU into the pedestal. Position the leveling bracket
(attached to the rear of the PDU) in the small opening toward the
front of the pedestal. The leveling bracket will support the back of
the PDU.
2
Install the NT7D10CA system monitor assembly:
a
Connect the small orange connectors (J2 on the PDU, P2 on the
system monitor assembly) on the left side of the PDU.
b
Connect the flat white connector to the small circuit board (P1 on the
PDU, J1 on the system monitor assembly) on the right side of the
PDU.
c
Guide the connector on the free end of the system monitor ribbon
cable (from J2) up through the hole in the top of the pedestal and
connect it to module 0.
d
Install and tighten the two vertical screws that attach the L-bracket
to the PDU.
e
Gently push the system monitor assembly into the pedestal.
3
Tighten the screws that secure the PDU and the system monitor
assembly.
4
Reconnect the remaining cables from module 0:
a
Reconnect the large orange power connector (J1).
b
Replace the I/O safety panel.
c
Replace the rear cover to the module.