Asr And Inertia Tuning - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

Table 4.13 Auto-Tuning Input Data in EZ Open Loop Vector Control Method
Input Data
Motor Type Selection
Motor Max Revolutions
Motor Rated Revolutions
Motor Rated Frequency
Motor Rated Voltage
PM Motor Rated Current (FLA)
PM Motor Rated Power (kW)
Number of Motor Poles

ASR and Inertia Tuning

To increase drive responsiveness and prevent hunting, use Auto-Tuning to automatically adjust the control-related
parameters. These types of Auto-Tuning are available for the control system:
• Deceleration Rate Tuning
• KEB Tuning
Note:
If you do Control Tuning, you cannot set H1-xx = 61 [Motor 2 Select]. Do not do Control Tuning for applications that switch between
motor 1 and motor 2.
Parameter
Mode
Settings
Deceleration Rate
T3-00 = 2
Tuning
KEB Tuning
T3-00 = 3
Deceleration Rate Tuning
Deceleration Rate Tuning automatically sets the deceleration rate to prevent an ov [Overvoltage] fault during
motor deceleration. Set C1-11 [Accel/Decel Time Switchover Freq] first to automatically set parameters C1-02
[Decel Time 1] (high speed range) and C1-08 [Decel Time 4] (low speed range).
KEB Tuning
KEB Tuning automatically sets parameters used for the KEB Ride-Thru function and for the overvoltage
suppression function.
Control Tuning automatically sets these parameters in to the best values.
Parameters Automatically Set
C1-02 [Decel Time 1]
C1-08 [Decel Time 4]
C1-09 [Fast Stop Time]
L2-06 [KEB Decel Time]
L3-25 [Load Inertia Ratio]
*1
The drive automatically sets C1-08 [Decel Time 4] only when C1-11 [Ac/Dec Switch Frequency] ≠ 0.
*2
When L2-29 = 1 [KEB Method = Single KEB1 Ride-Thru], the drive will automatically adjust C1-09 [Fast Stop Time] and will not
adjust L2-06 [KEB Decel Time]. If you must not change the Fast Stop time, do not do KEB Tuning.
SIEPCYEUOQ2V01A Q2V Technical Manual
Parameter
T4-02
T4-03
T4-04
T4-05
T4-06
T4-07
T4-08
T4-09
Table 4.14 Control Loop Tuning Selection
Application Conditions and Benefits
To automatically adjust the deceleration rate to
prevent an ov [Overvoltage] fault.
• To automatically adjust parameter settings to
prevent an ov [Overvoltage] fault with the KEB
Ride-Thru function.
• When L3-11 = 1 [Overvolt Supression Select =
Enabled].
Table 4.15 Parameters set in Control Tuning
Unit
Motor Constant
(0)
-
-1
min
min
-1
Hz
V
A
kW
-
Applicable Control Methods (A1-02 Settings)
V/f Control
OLVector
OLVector
(0)
(2)
x
x
x
x
Deceleration Rate Tuning
x
*1
x
-
-
-
4.9 Auto-Tuning
Auto-Tuning Mode
(T4-01 Setting)
Static R Autotune
(1)
x
-
x
-
x
-
x
-
x
-
x
x
x
-
x
-
PM
PM
EZ Vector
AOLVector
(8)
(5)
(6)
x
x
x
x
x
x
KEB Tuning
-
-
*2
x
*3
x
x
127